top of page

SENTRY

4 pole Digital Emergency Lighting Test Switch

Presented in a compact, DIN-mountable form factor for easy installation in a switchboard, Sentry simulates mains failure for a 90 or 120 minute duration via a user-selectable switch.


In accordance with AS2293.2, manual discharge facilities for emergency lighting installations must be key-operated and automatically reverts back to its normal state upon completion of the discharge test.


A 120 minute commissioning test shall be conducted for all new installations (the first discharge), followed by a 90 minute in-service discharge test every 6 months thereafter.

SKU: ETS-SENTRY

 

Features:

  • 4 pole (up to 4 lighting circuits)

  • 16 Amp contactor

  • Key-operated

  • 90 min or 120 min selectable

  • Fully electronic and digitally controlled

  • Digital timer display

  • DIN-rail mounted (optional MCB enclosure available)

  • Low standby energy consumption

  • Automatically reverts back to original state as soon as discharge is completed

  • 3 year warranty

  • Designed and tested in accordance to AS/NZS 2293.1

 